Why is my underfloor heating losing pressure?
Wet underfloor heating (UFH) is a sealed system, the same as radiators. If the gauge keeps falling, water is getting out. In a UFH system there are only a handful of places it can go: the manifold and its fittings, the pump and mixing set, the connections where each loop joins the manifold, the loop pipe under the floor, or the boiler or heat pump that feeds it all.
This page covers the checks you can do yourself with the gauge and the manifold valves. They will not show you the exact spot under the floor. What they do tell you is whether the leak is under the floor at all and, if it is, which loop. That changes the visit: an engineer who knows the loop goes straight to that room. Once the loop is known, our guide to how engineers find a leak in underfloor heating pipes explains how the spot is pinned down.
The loops are normally one continuous length of pipe with no joints under the floor, so a leak in a loop nearly always has a physical cause. A screw or nail is the usual one, from skirting, door thresholds, kitchen units or a new floor finish. Think about what has been fixed to the floor since the heating went in. It often tells you which loop to test first.
Which gauge should you be watching?
Work out how the system is plumbed before you start, because it decides which gauge tells you anything.
- UFH run from a combi or system boiler through a mixing unit. The UFH shares water with the radiators. The boiler gauge reads the whole system, so a drop could be in a radiator circuit or under the floor.
- UFH run from a heat pump. The heat pump circuit usually has its own gauge near the indoor unit or cylinder. The manifold may be the only emitter on it.
- A manifold with its own gauge. Some manifolds carry a small gauge. It only reads the system pressure while the manifold is open to the rest of the system.
If radiators share the circuit, read our guide to what to do when a boiler keeps losing pressure as well, because the leak may not be under the floor at all.
How do you take readings that mean something?
Read the gauge cold, at the same time each morning, before the heating comes on. Write down the date and the figure. Warm water expands, so a reading taken while the floor is heating sits higher, and comparing a hot reading with a cold one can make a sound system look as if it is leaking. A few days of cold readings gives you a loss rate, such as a tenth of a bar a day. Every check below is measured against that figure.
Look out for the opposite too. If the pressure creeps up overnight with the heating off, the filling loop valve is probably letting water in. That is not a leak, but it can hide one, because water coming in can balance water going out under the floor. Close both filling loop valves firmly before you start, and disconnect the braided hose if yours is the removable type.
Can the leak be at the manifold?
Yes, and it is the first place to look because you can see it. Take the cover off the manifold cabinet and go over each of these with a torch and a dry tissue:
- The compression or push-fit connections where each loop pipe joins the flow and return bars.
- The flow meters or balancing valves on the flow bar. The small sight glasses can weep at their seals.
- The valve bodies under the actuator heads on the return bar. Pull an actuator off gently and look at the valve pin for moisture or crusting.
- The pump, its unions and the blending or mixing valve.
- The automatic air vents and drain cocks at the ends of the bars.
- The floor directly under the manifold, where slow drips collect at the back of the cabinet.
A white or green crust, a tide mark or damp screed under the manifold is enough to point the search there. Do not tighten fittings on a pressurised manifold unless you know the fitting type. Leave that to a heating engineer.
How do you isolate underfloor heating loops one at a time?
Each loop has a valve at both ends: a flow meter or lockshield on the flow bar, and a valve under an actuator on the return bar. Closing both ends takes that loop out of the system. If the gauge stops falling while a loop is shut, that loop is the one leaking.
- Turn the heating off and let the floor cool. Your readings then compare with the cold baseline, and the pump is not running against closed loops.
- Record every flow meter setting before you touch it. Count the turns as you close each one and take a photo of the manifold. You need to reopen each loop to the same setting, or the balancing is lost.
- Isolate the whole manifold first. Close the main flow and return valves between the manifold and the boiler or heat pump, often red and blue handled ball valves. If the boiler gauge keeps falling at the same rate, the leak is on the boiler or radiator side, not under the floor.
- If the gauge holds, reopen the manifold and close one loop at both ends. On the return bar, take off the actuator and fit the manual cap that came with the manifold, then turn it clockwise to close. Close the flow meter for the same loop.
- Leave it long enough to see a change at your loss rate. If you lose half a bar a week, one day shows almost nothing. If you lose half a bar a day, overnight is enough.
- Reopen that loop to its recorded setting and close the next. Label each loop with the room it serves as you go.
- With a lot of loops, halve the search. Close half of them. If the drop stops, the leak is in that half, so split it again.
Stop and call an engineer if a valve will not turn, a flow meter starts to weep when you move it, or you cannot tell which valve belongs to which loop. Old manifold valves seize, and forcing one can turn a slow loss into a fast one.
What does each result tell you?
| What you see | What it points to | Next step |
|---|---|---|
| Gauge still falls with the whole manifold isolated | A leak on the boiler, the radiators or the pipework before the manifold | Check the boiler side and radiator valves first |
| Gauge holds with the manifold isolated and falls again when it is reopened | The manifold, its pump and mixing set, or a loop | Inspect the manifold again, then test loop by loop |
| Gauge stops falling while one loop is closed | That loop is leaking under the floor | Leave it closed and book a survey of that room |
| Gauge keeps falling whichever single loop is closed | A leak on the manifold body or pump set, or more than one loop leaking | Close all the loops together. If it still falls, the manifold side is the suspect |
| Steady when cold, lower after each heat-up | An expansion vessel that has lost its charge, with the relief valve letting water out when hot | Check the outside discharge pipe for drips during a heat-up |
| Pressure rises with the heating off | The filling loop is letting water in | Close the filling loop fully and start the readings again |
These checks use the system gauge, which reads in tenths of a bar. A very slow leak can take several days to show on it. An engineer's loop test uses a hand test pump and a more sensitive gauge to the pipe maker's figures, and BS EN 1264 calls for the same kind of test before the screed is laid. Your results tell the engineer where to start that test, not whether to skip it.
What should you tell the engineer?
Have these ready when you call: the cold loss rate from your readings, which loop or loops stopped the drop, the flow meter settings you wrote down, and the floor finish in that room. Say when anything was last screwed or fixed to the floor, such as kitchen units, a threshold strip or new flooring. If you have the installer's commissioning sheet or a drawing of the loop layout, dig it out. With that information the survey starts at the right loop instead of repeating the isolation from scratch.
When should you call a leak detection specialist?
Call a heating engineer for a weeping fitting at the manifold. Call a leak detection specialist when the manifold is dry and one loop stops the drop, when the drop carries on whichever loop is closed and you cannot find a weep, or when there is a warm or damp patch on the floor.
Our underfloor heating leak detection service uses loop testing, thermal imaging and tracer gas where needed. Under-floor leak detection is priced at £300 to £700 depending on the floor area, the number of loops and the methods required. If the leak is inside your own property and we cannot find it, there is no fee (see the terms). Call 020 3912 0200 to talk it through.
Frequently asked questions
How do I know if my underfloor heating is leaking?
The main signs are a system that needs regular topping up, a patch of floor that feels warmer or damper than the rest, lifting or staining of the floor finish, and one room heating poorly compared with the others.
How long should I leave each loop closed?
Long enough for your normal loss rate to show clearly on the gauge. For a fast leak that is overnight. For a slow one it can be two or three days per loop, which is why halving the loops saves time.
Should I keep running underfloor heating with a leak?
If the loss is slow and nothing shows on the floor, running it for short spells is usually fine. If water is appearing at the surface, close that loop at the manifold and get it looked at.
What pressure should underfloor heating be at?
It shares the pressure of the boiler or heat pump circuit that feeds it, and the boiler or heat pump manual gives the recommended cold figure. Most domestic sealed systems sit around 1 to 1.5 bar cold.
Can I use a leak sealer in underfloor heating?
Check with the pipe and manifold manufacturers first. Sealers can collect in flow meters, valves and narrow pipe, and they will not reliably close a hole made by a screw or nail.